Voltage Drop Calculator
Pick the wire, circuit type, voltage, current and run length to see the voltage drop and whether it meets the NEC 3% and 5% guidelines.
How to use the Voltage Drop Calculator
- Choose Conductor material.
- Choose Wire size.
- Choose Circuit type.
- Enter Source voltage (Line-to-line voltage for three-phase).
- Enter Load current.
- Fill in the remaining fields, or keep their sensible defaults.
- Read your answer in the results panel. It updates as you type, and the breakdown, step-by-step working and any charts or tables appear below it.
- Use Share link to save or send the exact calculation, or Copy to paste the results elsewhere.
Why voltage drop matters
Every wire has some resistance, so some voltage is lost along the run before current reaches the load. A small drop is normal. Too much drop makes motors run hot, makes lights dim and wastes energy as heat in the wire. Long runs, high currents and thin wires make it worse.
The formulas
For DC and single-phase AC, current flows out on one conductor and back on another, so the length counts twice:
Vdrop = 2 × L × R × I
For balanced three-phase circuits the return path is shared between phases, and the factor becomes √3:
Vdrop = √3 × L × R × I
Here L is the one-way length, R is the conductor resistance per unit length, and I is the load current. Percent drop is Vdrop ÷ source voltage × 100.
Resistance data used
AWG and kcmil sizes use the DC resistance of stranded, uncoated conductors at 75 °C from NEC Chapter 9, Table 8. Metric sizes use IEC 60228 class 2 values corrected to 75 °C. Aluminum has about 1.6 times the resistance of copper, so it needs to be roughly two AWG sizes larger to carry the same current with the same drop.
Worked example
A 120 V single-phase circuit feeds a 15 A load 100 ft away on 12 AWG copper (1.98 Ω per 1,000 ft):
- Vdrop = 2 × 100 × 0.00198 × 15 = 5.94 V
- Percent drop = 5.94 ÷ 120 = 4.95%
- Voltage at the load = 114.06 V
That is above the 3% guideline. Moving up to 10 AWG (1.24 Ω per 1,000 ft) brings it down to 3.72 V, or 3.1%, and 8 AWG gets it to about 1.9%. The table under the result shows every size for your circuit, so you can find the smallest one that passes.
NEC 3% and 5% guidance
Informational notes in the National Electrical Code suggest a maximum of 3% drop on a branch circuit or a feeder, and 5% in total from the service to the farthest outlet. These are recommendations, not hard rules, but many inspectors and engineers design to them. Sensitive electronics and motor loads benefit from staying well under 3%.
Limits of this estimate
- It uses DC resistance only. Large AC conductors also have reactance, which adds a little drop when the power factor is low.
- Conductor temperature changes resistance by about 0.4% per °C. A wire running cooler than 75 °C will drop slightly less.
- Voltage drop doesn’t size a wire for safety. Always check the ampacity tables and overcurrent protection rules too.
Frequently asked questions
What is an acceptable voltage drop?
The NEC recommends no more than 3% on a branch circuit or feeder and 5% overall. For a 120 V circuit that is 3.6 V and 6 V.
Should I enter the one-way or round-trip length?
Enter the one-way distance from the panel or source to the load. The formula already accounts for the return conductor.
How can I reduce voltage drop?
Use a larger wire, shorten the run, use a higher supply voltage (for example 240 V instead of 120 V), or split the load across more circuits.
Is aluminum wire worse than copper for voltage drop?
Aluminum has about 61% of the conductivity of copper, so the same size has around 1.6 times the drop. Choose a larger aluminum size to match copper performance.